46 CFR 112.05-3: -3 Main-emergency bus-tie.
Where this section sits in the code
- Title 46—Shipping
- CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
- SUBCHAPTER J—ELECTRICAL ENGINEERING
- PART 112—EMERGENCY LIGHTING AND POWER SYSTEMS
- Subpart 112.05—General
Each bus-tie between a main switchboard and an emergency switchboard must:
(a) Disconnect automatically upon loss of potential at the emergency switchboard;
(b) Be arranged to prevent parallel operation of an emergency power source with any other source of electric power, except for interlock systems for momentary transfer of loads; and
(c) If arranged for feedback operation, open automatically upon overload of the emergency power source before the emergency power source is tripped off the line from the overload.