46 CFR 132.110: Piping.
Where this section sits in the code
- Title 46—Shipping
- CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
- SUBCHAPTER L—OFFSHORE SUPPLY VESSELS
- PART 132—FIRE-PROTECTION EQUIPMENT
- Subpart A—General Provisions; Fire Main
(a) Except as provided for liftboats by § 134.180 of this subchapter, each fitting, flange, valve, and run of piping must meet the applicable requirements of part 128 of this subchapter. Piping must be—
(1) Hot-dip galvanized;
(2) At least extra-heavy schedule; or
(3) Of a suitable corrosion-resistant material.
(b) Each distribution cut-off valve must be marked in compliance with § 131.820 of this subchapter.