46 CFR 61.30-10: -10 Hydrostatic test.
Where this section sits in the code
- Title 46—Shipping
- CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
- SUBCHAPTER F—MARINE ENGINEERING
- PART 61—PERIODIC TESTS AND INSPECTIONS
- Subpart 61.30—Tests and Inspections of Fired Thermal Fluid Heaters
All new installations of thermal fluid heaters must be given a hydrostatic test of 1 1/2 times the maximum allowable working pressure. The test must be conducted in the presence of a marine inspector. No subsequent hydrostatic tests are required unless, in the opinion of the Officer in Charge Marine Inspection, the condition of the heater warrants such a test. Where hydrostatic tests are required, an inspection is made of all accessible parts under pressure. The thermal fluid may be used as the hydrostatic test medium.