49 CFR 192.204: Risers installed after January 22, 2019.
Where this section sits in the code
- Title 49—Transportation
- Subtitle B—Other Regulations Relating to Transportation
- CHAPTER I—PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION, DEPARTMENT OF TRANSPORTATION
- SUBCHAPTER D—PIPELINE SAFETY
- PART 192—TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS
- Subpart D—Design of Pipeline Components
(a) Riser designs must be tested to ensure safe performance under anticipated external and internal loads acting on the assembly.
(b) Factory assembled anodeless risers must be designed and tested in accordance with ASTM F1973 (incorporated by reference, see § 192.7).
(c) All risers used to connect regulator stations to plastic mains must be rigid and designed to provide adequate support and resist lateral movement. Anodeless risers used in accordance with this paragraph must have a rigid riser casing.