49 CFR 192.706: Transmission lines: Leakage surveys.
Where this section sits in the code
- Title 49—Transportation
- Subtitle B—Other Regulations Relating to Transportation
- CHAPTER I—PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION, DEPARTMENT OF TRANSPORTATION
- SUBCHAPTER D—PIPELINE SAFETY
- PART 192—TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS
- Subpart M—Maintenance
Leakage surveys of a transmission line must be conducted at intervals not exceeding 15 months, but at least once each calendar year. However, in the case of a transmission line which transports gas in conformity with § 192.625 without an odor or odorant, leakage surveys using leak detector equipment must be conducted—
(a) In Class 3 locations, at intervals not exceeding 7 1/2 months, but at least twice each calendar year; and
(b) In Class 4 locations, at intervals not exceeding 4 1/2 months, but at least four times each calendar year.
Collected 2026-08-27T02:26:34Z. Source file · JSON