N.Y.C. Admin. Code § 210.52: Section 210.52
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 11: The New York City Electrical Code
Section 210.52(J) – Add a new Section 210.52(J) to read as follows:
(J) Outlet Requirements For Residential-Type Occupancies. In addition to the requirements set forth in (A) through (I) of this section, living rooms, bedrooms, dining rooms or similar rooms shall have at least 1 receptacle outlet installed for air conditioners. Such receptacle outlets shall be supplied by an individual branch circuit.
Exception: For buildings with central air conditioning systems, a separate receptacle outlet shall not be required in any living room, bedroom, dining room, or other similar room served by such system.