N.Y.C. Admin. Code § BC 707: Section BC 707: Fire Barriers
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 7: New York City Building Code
707.1 General.
Fire barriers installed as required elsewhere in this code or the New York City Fire Code, shall comply with this section.
707.2 Materials.
Fire barriers shall be of materials permitted by the building type of construction.
707.3 Fire-resistance rating.
The fire-resistance rating of fire barriers shall comply with this section.
707.3.1 Shaft enclosures.
The fire-resistance rating of the fire barrier separating building areas from a shaft shall comply with Section 713.4.
707.3.2 Interior exit stairway and ramp construction.
The fire-resistance rating of the fire barrier separating building areas from an interior exit stairway or ramp shall comply with Section 1023.1.
707.3.3 Enclosures for exit access stairways.
The fire-resistance rating of the fire barrier separating building areas from an exit access stairway or ramp shall comply with Section 713.4.
707.3.4 Exit passageway.
The fire-resistance rating of the fire barrier separating building areas from an exit passageway shall comply with Section 1024.3.
707.3.5 Horizontal exit.
The fire-resistance rating of the separation between building areas connected by a horizontal exit shall comply with Section 1026.1.
707.3.6 Atriums.
The fire-resistance rating of the fire barriers separating atriums shall comply with Section 404.6.
707.3.7 Incidental uses.
The fire barrier separating incidental uses from other spaces in the building shall have a fire-resistance rating of not less than that indicated in Table 509.
707.3.8 Control areas.
Fire barriers separating control areas shall have a fire-resistance rating of not less than that required in Section 414.2.4.
707.3.9 Separated occupancies.
Where the provisions of Section 508.4 are applicable, the fire barrier separating mixed occupancies shall have a fire-resistance rating of not less than that indicated in Table 508.4 based on the occupancies being separated.
707.3.10 Fire areas.
The fire barriers or horizontal assemblies, or both, separating a single occupancy into different fire areas shall have a fire-resistance rating of not less than that indicated in Table 707.3.10. The fire barriers or horizontal assemblies, or both, separating fire areas of mixed occupancies shall have a fire-resistance rating of not less than the highest value indicated in Table 707.3.10 for the occupancies under consideration.
Exception: For fire-resistance ratings of public corridors, see Section 707.3.11.
Table 707.3.10 Fire-Resistance Rating Requirements for Fire Barrier Assemblies or Horizontal Assemblies Between Fire Areas
Occupancy Group
Fire-Resistance Rating (hours)
H-1, H-2
4
F-1, H-3, S-1
3
A, B, E, F-2, H-4, H-5, I, M, R, S-2
2
U
1
707.3.11 Public corridors.
The fire-resistance rating of public corridor walls shall comply with Table 1020.1.2.
707.4 Exterior walls.
Where exterior walls serve as a part of a required fire-resistance-rated shaft, stairway or ramp enclosure, or separation, such walls shall comply with the requirements of Section 705 for exterior walls and the fire-resistance-rated enclosure or separation requirements shall not apply.
Exception: Exterior walls required to be fire-resistance-rated in accordance with Section 1021 for exterior egress balconies, Section 1023.7 for interior exit stairways and ramps and Section 1027.6 for exterior exit stairways and ramps.
707.5 Continuity.
Fire barriers shall extend from the top of the floor/ceiling assembly below to the underside of the floor or roof sheathing, slab or deck above and shall be securely attached thereto. Such fire barriers shall be continuous through concealed spaces, such as the space above a suspended ceiling. Joints and voids at intersections shall comply with Sections 707.8 and 707.9.
Exceptions:
1. Shaft enclosures shall be permitted to terminate at a top enclosure complying with Section 713.12.
2. Interior exit stairway and ramp enclosures required by Section 1023 and exit access stairway and ramp enclosures required by Section 1019 shall be permitted to terminate at a top enclosure complying with Section 713.12.
707.5.1 Supporting construction.
The supporting construction for a fire barrier shall be protected to afford the required fire-resistance rating of the fire barrier supported. Hollow vertical spaces within a fire barrier shall be fireblocked in accordance with Section 718.2 at every floor level.
Exceptions:
1. The maximum required fire-resistance rating for assemblies supporting fire barriers separating tank storage as provided for in Section 415.9.1.2 shall be 2 hours, but not less than required by Table 601 for the building construction type.
2. Supporting construction for 1-hour fire barriers required by Table 509 in buildings of Type IIB, IIIB and VB construction is not required to be fire-resistance rated unless required by other sections of this code.
707.6 Openings.
Openings in a fire barrier shall be protected in accordance with Section 716. Openings shall be limited to a maximum aggregate width of 25 percent of the length of the wall, and the maximum area of any single opening shall not exceed 156 square feet (14.5 m
2
). Openings in enclosures for exit access stairways and ramps, interior exit stairways and ramps and exit passageways shall also comply with Sections 1019, 1023.4 and 1024.5, respectively.
Exceptions:
1. Openings shall not be limited to 156 square feet (14.5 m
2
) where adjoining floor areas are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
2. Openings shall not be limited to 156 square feet (14.5 m
2
) or an aggregate width of 25 percent of the length of the wall where the opening protective is a fire door serving enclosures for exit access stairways and ramps, and/or interior exit stairways and ramps.
3. Openings shall not be limited to 156 square feet (14.5 m
2
) or an aggregate width of 25 percent of the length of the wall where the opening protective has been tested in accordance with ASTM E 119 or UL 263 and has a minimum fire-resistance rating not less than the fire-resistance rating of the wall.
4. Fire window assemblies permitted in atrium separation walls shall not be limited to a maximum aggregate width of 25 percent of the length of the wall.
5. Openings shall not be limited to 156 square feet (14.5 m
2
) or an aggregate width of 25 percent of the length of the wall where the opening protective is a fire door assembly in a fire barrier separating an enclosure for exit access stairways and ramps, and/or interior exit stairways and ramps from an exit passageway in accordance with Section 1023.3.1.
6. Openings permitted in atrium enclosures shall comply with the provisions of Section 404.5.
707.7 Penetrations.
Penetrations of fire barriers shall comply with Section 714.
707.7.1 Prohibited penetrations.
Penetrations into enclosures for exit access stairways and ramps, interior exit stairways and ramps, and exit passageways shall be allowed only where permitted by Sections 1019, 1023.5 and 1024.6, respectively.
707.8 Joints.
Joints made in or between fire barriers, and joints made at the intersection of fire barriers with underside of a fire-resistance-rated floor or roof sheathing, slab or deck above, and the exterior vertical wall intersection shall comply with Section 715.
707.9 Voids at intersections.
The voids created at the intersection of a fire barrier and a nonfire-resistance-rated roof assembly or a nonfire-resistance-rated exterior wall assembly shall be filled. An approved material or system, or a material consistent with the construction requirements of the fire barrier, shall be used to fill the void, and shall be securely installed in or on the intersection for its entire length so as not to dislodge, loosen or otherwise impair its ability to accommodate expected building movements and to retard the passage of fire and hot gases.
707.10 Ducts and air transfer openings.
Penetrations in a fire barrier by ducts and air transfer openings shall comply with Section 717.
707.10.1 Prohibited ducts and air transfer openings.
Penetrations by ducts and air transfer openings into an enclosure for exit access stairways and ramps shall only be allowed when permitted by Sections 1023.4 and 1023.6.