N.Y.C. Admin. Code § FC 2704: Section FC 2704: Storage
Where this section sits in the code
- New York City Administrative Code
- Title 29
- Chapter 2: New York City Fire Code
2704.1 General.
Hazardous materials shall be stored in semiconductor fabrication facilities in accordance with this section and the provisions of other applicable chapters of this code.
2704.2 Fabrication areas.
Hazardous materials shall be stored in accordance with FC 2704.2.1 through 2704.2.2.1.
2704.2.1 Location of HPM storage in fabrication areas.
Storage of HPM in fabrication areas shall be within approved or listed storage cabinets, gas cabinets or within a workstation as follows:
1. Flammable and combustible liquid storage cabinets shall comply with the requirements of FC Chapter 57.
2. Hazardous materials storage cabinets shall comply with the requirements of FC 5003.8.7.
3. Gas cabinets shall comply with the requirements of FC 5003.8.6. Gas cabinets for highly toxic or toxic gases shall additionally comply with the requirements of FC 6004.1.2.
4. Exhausted enclosures shall comply with FC 5003.8.5. Exhausted enclosures for highly toxic or toxic gases shall also comply with FC 6004.1.3.
5. Workstations shall comply with the requirements of FC 2705.2.3.
2704.2.2 Maximum aggregate quantities in fabrication areas.
The aggregate quantities of hazardous materials stored, handled and used in a single fabrication area shall be limited as specified in this section.
Exception: Fabrication areas containing quantities of hazardous materials not exceeding the maximum allowable quantities per control area established by FC 5003.1.1, 5704.3.4 and 5704.3.5.
FC Table 2704.2.2.1 Quantity Limits for Hazardous Materials in a Single Fabrication Area in Group H-5
a
Hazard Category
Solids (pounds / square foot)
Liquids (gallons / square foot)
Gas (SCF / square foot)
Physical-Hazard Materials
Combustible dust
Note b
Not Applicable
Not Applicable
Combustible fiber
Loose
Baled
Note b Notes b, c
Not Applicable
Not Applicable
Combustible liquid
Class II
Class IIIA
Class IIIB
Combination Class I, II and IIIA
Not Applicable
0.01 0.02 Not Limited 0.04
Not Applicable
Cryogenic gas
Flammable
Oxidizing
Not Applicable
Not Applicable
Note d 1.25
Explosives
Note b
Note b
Note b
Flammable gas
Gaseous
Liquefied
Not Applicable
Not Applicable
Note d Note d
Flammable liquid
Class IA
Class IB
Class IC
Combination Class IA, IB and IC
Combination Class I, II and IIIA
Not Applicable
0.0025 0.025 0.025 0.025 0.04
Not Applicable
Flammable solid
0.001
Not Applicable
Not Applicable
Organic peroxide
Unclassified detonable
Class I
Class II
Class III
Class IV
Class V
Note b Note b 0.025 0.1 Not Limited Not Limited
Not Applicable
Not Applicable
Oxidizing gas
Gaseous
Liquefied
Combination of Gaseous and Liquefied
Not Applicable
Not Applicable
1.25 1.25 1.25
Oxidizer
Class 4
Class 3
Class 2
Class 1
Combination oxidizer Class 1, 2, 3
Note b 0.003 0.003 0.003 0.003
Note b 0.03 0.03 0.03 0.03
Not Applicable
Pyrophoric
Note b
0.00125
Notes d and e
Unstable reactive
Class 4
Class 3
Class 2
Class 1
Note b 0.025 0.1 Not Limited
Note b 0.0025 0.01 Not Limited
Note b Note b Note b Not Limited
Water reactive
Class 3
Class 2
Class 1
Note b 0.25 Not Limited
0.00125 0.025 Not Limited
Not Applicable
Health-Hazard Materials
Corrosives
Not Limited
Not Limited
Not Limited
Highly toxics
Not Limited
Not Limited
Note d
Toxics
Not Limited
Not Limited
Note d
For SI: 1 pound per square foot = 4.882 kg/m
2
, 1 gallon per square foot = 0.025 L/m
2
, 1 cubic foot = 0.02832 m
3
.
a. Hazardous materials within piping shall not be included in the calculated quantities.
b. Quantity of hazardous materials in a single fabrication area shall not exceed the maximum allowable quantities per control area in FC Tables 5003.1.1(1) and 5003.1.1(2).
c. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.
d. The aggregate quantity of flammable, pyrophoric, toxic and highly toxic gases shall not exceed 9,000 SCF.
e. The aggregate quantity of pyrophoric gases in the building shall not exceed the amounts set forth in FC Table 5003.8.2.
2704.2.2.1 Storage and use in fabrication areas.
The maximum quantities of hazardous materials stored in a single fabrication area shall not exceed the quantities set forth in FC Table 2704.2.2.1.
2704.3 Indoor storage outside of fabrication areas.
The indoor storage of hazardous materials outside of fabrication areas shall be in accordance with FC 2704.3.1 through 2704.3.3.
2704.3.1 HPM storage.
The indoor storage of HPM in quantities greater than those listed in FC 5003.1.1 and 5704.3.4 shall be in a room complying with the requirements of the construction codes, including the Building Code,
and this code for a liquid storage room, HPM room or gas room as appropriate for the materials stored.
2704.3.2 Other hazardous materials storage.
The indoor storage of other hazardous materials shall comply with the requirements of FC 5001, 5003 and 5004 and other applicable provisions of this code.
2704.3.3 Separation of incompatible hazardous materials.
Incompatible hazardous materials in storage shall be separated from each other in accordance with FC 5003.9.8.
2704.4 Exit access corridors and exit enclosures.
Hazardous materials shall not be stored in exit access corridors or exit access enclosures.