N.Y.C. Admin. Code § FGC 609: Section FGC 609: Floor Furnaces
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 9: New York City Fuel Gas Code
609.1 General.
Floor furnaces shall be tested in accordance with ANSI Z21.86/CSA 2.32 and shall be installed in accordance with the manufacturer's instructions.
609.2 Placement.
The following provisions apply to floor furnaces:
1.
Floors. Floor furnaces shall not be installed in the floor of any doorway, stairway landing, aisle or passageway of any enclosure, public or private, or in a means of egress from any such room or space.
2.
Walls and corners. The register of a floor furnace with a horizontal warm-air outlet shall not be placed closer than 6 inches (152.4 mm) to the nearest wall. A distance of not less than 18 inches (457.2 mm) from two adjoining sides of the floor furnace register to walls shall be provided to eliminate the necessity of occupants walking over the warm-air discharge. The remaining sides shall be permitted to be placed not closer than 6 inches (152.4 mm) to a wall. Wall-register models shall not be placed closer than 6 inches (152.4 mm) to a corner.
3.
Draperies. The furnace shall be placed so that a door, drapery or similar object cannot be nearer than 12 inches (304.8 mm) to any portion of the register of the furnace.
4.
Floor construction. Floor furnaces shall be located so as to be readily accessible. Means shall be provided for supporting the furnace when the grille is removed. Floor furnaces shall be installed only on floors of noncombustible construction having at least a two-hour fire rating, except that floor furnace enclosures in one-and two- family dwellings shall be constructed of non-combustible materials with a fire-resistance rating of not less than one hour.
5.
Thermostat. The controlling thermostat for a floor furnace shall be located within the same room or space as the floor furnace or shall be located in an adjacent room or space that is permanently open to the room or space containing the floor furnace.
609.3 Bracing.
The floor around the furnace shall be braced and headed with a support framework designed in accordance with the New York City Building Code.
609.4 Clearance.
The lowest portion of the floor furnace shall have not less than a 6-inch (152.4 mm) clearance from the grade level; except where the lower 6 inch (152.4 mm) portion of the floor furnace is sealed by the manufacturer to prevent entrance of water, the minimum clearance shall be not less than 2 inches (50.8 mm). Where such clearances cannot be provided, the ground below and to the sides shall be excavated to form a pit under the furnace so that the required clearance is provided beneath the lowest portion of the furnace. A 12 inch (304.8 mm) minimum clearance shall be provided on all sides except the control side, which shall have an 18 inch (457.2 mm) minimum clearance.
609.5 Reserved.
609.6 Reserved.
609.7 Enclosures.
Enclosures of floor furnaces shall be constructed entirely of noncombustible materials with a fire-resistance rating of at least 1-hour and the enclosure shall be provided with adequate outdoor air to ensure proper combustion. The enclosure shall be provided with adequate means of access for servicing the furnace.
609.8 Duct temperature.
The outlet duct temperature of warm air heating furnaces shall not be greater than 250°F (121.1°C).
609.9 One- and two-family dwellings.
Floor furnace enclosures shall be constructed of non-combustible materials with a fire-resistance rating of at least one-hour. Means shall be provided for supporting the furnace when the grille is removed. Clearances shall be provided as per NFPA 54.