N.Y.C. Admin. Code § FGC_AppE.2: E.2 Gas regulator and gas regulator vent outlets.

Read at publisher ↗
Where this section sits in the code
  1. New York City Administrative Code
  2. Title 28
  3. Chapter 9: New York City Fuel Gas Code

Gas meter piping supplying gas to a building at a pressure in excess of 1/2 psig (3.4 kPa gauge) shall be provided with a regulator that will reduce the pressure of the gas to 1/2 psig (3.4 kPa gauge) or less prior to entering the gas distribution piping in the building, except where the use of higher pressure is permitted. Where gas distribution pressure in excess of 1/2 psig (3.4 kPa gauge) is permitted, it shall be regulated to not exceed the maximum pressure level as permitted by the code or the commissioner.

E.2.1 Inside gas meter piping operating at a pressure in excess of 15 psig (103.4 kPa gauge) shall comply with the following:

1. Where such piping is greater than 4 inches (101.6 mm) in diameter, the meter piping shall be installed in a properly ventilated meter room of 3-hour fire rated construction.

2. The maximum total developed length from the outlet of the service head valve to the inlet of the farthest regulator shall be limited as follows:

Service Line Valve Size 

Maximum Distance (Linear Feet of Pipe)

Up to 2 inch (51 mm) pipe size

4 feet (1219 mm)

Over 2 inch (51 mm) through 4 inch (102 mm) pipe size

8 feet (2438 mm)

Over 4 inch (102 mm) through 8 inch (203 mm) pipe size

15 feet (4572 mm)

10 inch (254 mm) pipe size and larger

20 feet (6096 mm)

3. Where these maximum distances cannot be met, the following shall be required:

Footage (Linear Feet of Pipe) in Excess of Above Requirements

Additional Requirements 

Up to 5 feet (1534 mm)

The meter room shall have 3-hour fire-rating construction and adequate ventilation

Over 5 feet (1524 mm) through 10 feet (3048 mm)

Above requirements plus a combustible gas-detection alarm system

Over 10 (3048 mm) feet through 15 feet (4572 mm)

Above requirements plus special inspection by the customer or his representative as required by the New York City Building Code.

Over 15 feet (4572 mm) through 20 feet (6096 mm)

Above requirements plus (i) automatic gas shutoff devices; and (ii) explosion venting per NFPA 68 and NFPA 69 or alternative ventilation acceptable to the commissioner

Over 20 feet (6096 mm)

Above requirements plus suitable fire protection approved by the commissioner

For new gas installations made in existing structures, the above requirements shall be used to the extent feasible. Alternate designs may be considered by the commissioner.

E.2.2 When located inside the building, each regulator shall be provided with a vent pipe that leads directly to the outdoor air. The vent pipe shall be sized according to local utility requirements. The vent outlet shall not be located under a window or any opening leading back into the premises or located below any overhang or projection. No gas regulator vent outlet shall be covered over, plugged up, or otherwise obstructed, and all gas vents shall be identified by suitable marking on the outlet on the outside of the building. For buildings located in flood hazard areas, gas regulator vent outlets shall be installed in accordance with the additional requirements of Appendix G of the New York City Building Code.