N.Y.C. Admin. Code § FGC_AppE.3: E.3 Gas meter location.
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 9: New York City Fuel Gas Code
Gas meter location shall comply with the following:
1. When located inside the building, meters shall be located as near as practicable to the point of entrance of the service and, where possible, the meters shall be located in the cellar or basement unless otherwise permitted by the commissioner. The meter location shall be clean, dry, and free of refuse, steam or chemical fumes and located not less than 3 feet (914.4 mm) from any source of ignition or any source of heat which might cause damage to the meter. Meters shall be adequately protected against extreme cold or heat and shall be readily accessible for reading and inspection. The area in which the meter is located shall be properly ventilated as per Section E.4. Notwithstanding the foregoing, outside meter installation shall be permitted in areas where the utility company certifies that dry gas is being distributed.
Exception: Gas meter locations in one- and two-family dwellings shall not require ventilation.
2. No gas meter, other than the replacement of an existing meter shall be located in any boiler room or other room or space containing a heating boiler, in any stair hall, nor in any public hall above the cellar or above the lowest story if there is no cellar.
3. Gas meter rooms, when provided, shall at all times be kept clear of all rubbish; and shall not be used in any way for storage purposes, including material or equipment of any kind. A legible sign reading "Gas meter room – No storage permitted" shall be permanently and conspicuously posted on the exterior of the meter room door, except that the sign may be posted on the interior of the meter room door in occupancy group R-3. The lettering of such signs shall be of bold type at least one inch (25.4 mm) in height and shall be properly spaced to provide good legibility. The lettering and background shall be of contrasting colors. Where gas meters and related equipment are not located in a separate room but are located in an open floor area, no combustible material shall be stored or kept within five feet of such equipment; nor shall the gas meter be within 3 feet (914.4 mm) of any heating boiler or sources of ignition and, except occupancy group R-3, there shall be a physical barrier required if the room is also used for storage purposes or the like.
4. The installation of gas meter piping shall be made in accordance with the requirements of this code and the local utility company.
5. Piping containing gas with a pressure exceeding 1/2 psig (3.4 kPa gauge) and the gas service pressure regulator which may be subjected to accidental vehicular impact shall be suitably protected.