N.Y.C. Admin. Code § PC 305: Section PC 305: Protection of Pipes and Plumbing System Components
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 6: New York City Plumbing Code
305.1 Corrosion.
Pipes passing through or encased in concrete or cinder walls and floors or other corrosive material shall be protected against external corrosion by a protective sheathing or wrapping or other means that will withstand any reaction from the lime and acid of concrete, cinder or other corrosive material. Sheathing or wrapping shall allow for movement including expansion and contraction of piping to prevent any rubbing action. Thickness of sheathing or wrapping material shall be not less than 0.025 inch (0.64 mm).
305.2 Stress and strain.
Piping in a plumbing system shall be installed so as to prevent strains and stresses that exceed the structural strength of the pipe. Where necessary, provisions shall be made to protect piping from damage resulting from expansion, contraction and structural settlement.
305.3 Pipes through or under footings or foundation walls.
Any pipe that passes under a footing or through a foundation wall shall be provided with a relieving arch, or a pipe sleeve pipe shall be built into the foundation wall. The sleeve shall be two pipe sizes greater than the pipe passing through the wall.
305.4 Freezing.
Water, soil and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision is made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 48 inches (1219 mm) below grade.
305.4.1 Building sewer and building drain depth.
Building drains that connect to private sewage disposal systems shall be a minimum of 36 inches (914 mm) below finished grade at the point of septic tank connection. Building sewers and drains shall be a minimum of 36 inches (914 mm) below grade.
305.5 Waterproofing of openings.
Joints at the roof and around vent pipes, shall be made water tight by the use of lead, copper, galvanized steel, aluminum, plastic or other approved flashings or flashing material. Exterior wall openings shall be made water tight.
305.6 Protection against physical damage.
In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1 1/2 inches (38 mm) from the nearest edge of the member, the pipe shall be protected by steel shield plates. Such shield plates shall have a thickness of not less than 0.0575 inch (1.463 mm) (No. 16 gage). Such plates shall cover the area of the pipe where the member is notched or bored, and shall extend not less than 2 inches (51 mm) above sole plates and below top plates.
305.7 Protection of components of plumbing system.
Components of a plumbing system installed along alleyways, driveways, parking garages or other locations exposed to damage shall be recessed into the wall or otherwise protected in an approved
manner.
305.8 Breakage.
Pipes passing through or under walls shall be protected from breakage.
305.9 Wind resistance.
Equipment, appliances and supports that are exposed to wind shall be designed and installed to resist the wind pressures determined in accordance with the