704.1 Slope of horizontal drainage piping.
Horizontal drainage piping shall be installed in uniform alignment at uniform slopes. The slope of a horizontal drainage pipe shall be not less than that indicated in
Table 704.1
.
Table 704.1 Slope of Horizontal Drainage Pipe
Size (inches)
Minimum Slope (inch per foot)
2 1/2 or less
1/4
3 to 6
1/8
8 or larger
1/16
For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.33 mm/m.
704.2 Change in size.
The size of the drainage piping shall not be reduced in size in the direction of the flow. A 4-inch by 3-inch (102 mm by 76 mm) water closet connection shall not be considered as a reduction in size.
704.3 Connections to offsets and bases of stacks.
Horizontal branches shall connect to the bases of stacks at a point located not less than 10 times the diameter of the drainage stack downstream from the stack. Horizontal branches shall connect to horizontal stack offsets at a point located not less than 10 times the diameter of the drainage stack downstream from the upper stack.
704.4 Future fixtures.
Drainage piping for future fixtures shall terminate with an approved cap or plug.
704.5 Dead ends.
In the installation or removal of any part of a drainage system, dead ends shall be prohibited. Cleanout extensions and approved future fixture drainage piping shall not be considered as dead ends.
704.6 Suds Pressure Zones Vents.
Where sinks, laundry trays, laundry washing machines, bathtubs, and similar fixtures in which detergents producing suds are normally used and discharged at an upper floor level into a soil or waste stack that also serves fixtures in other occupancy units at a lower floor level, the drainage and vent piping for such lower fixtures shall be arranged so as to avoid connection to suds pressure zones in the sanitary drainage and vent systems. If connected to the sanitary system, a suds relief vent relieving to a nonpressure zone shall be provided at each suds pressure zone where such connections are installed. The diameter of such relief vent shall be at least 3/4 the diameter of the piping in which the pressure zone occurs, but not less than 2 inches (51 mm). Suds pressure zones shall be considered to exist at the following locations in sanitary drainage and vent systems when the piping serves fixtures on two or more floors that receive wastes that contain detergents producing suds:
1. In a soil or waste stack a zone shall be considered to exist in the vertical portion within 40 stack diameters of the base fitting.
2.
In the horizontal drain at the base of a soil or waste stack a zone shall be considered to exist in the horizontal portion within 10 stack diameters of the base fitting. Where a 60-degree (1.05 rad) or 90-degree (1.57 rad) fitting is installed in the horizontal drain, a zone shall be considered to exist in the horizontal portion within 40 drain diameters upstream of and 10 drain diameters downstream of the fitting in accordance with
Figure 704.6
.
3. In a soil or waste stack offset of 60 degrees (1.05 rad) or 90 degrees (1.57 rad), a zone shall be considered to exist in the vertical portion of the stack within 40 stack diameters of the base fitting for the upper section of the stack. The zone shall be considered to exist in the horizontal offset within 10 stack diameters of such base fitting and within 40 stack diameters of the top fitting for the lower section of the stack.
4. In a vent stack that has its base connected to a suds pressure zone in the sanitary drainage system, a zone shall be considered to exist in the portion of the vent stack extending from its base connection up to the lowest branch vent fitting located above the level of the suds pressure zone in the sanitary drainage system.
Figure 704.6 Suds Pressure Zones
704.7 Collection pipe labeling and marking.
Collection piping that conveys untreated water for reuse shall be painted gray in color or covered in a gray jacket and shall be labeled, embossed, or integrally stamped or marked, with the words: "CAUTION: UNTREATED WATER FOR RE-USE" or the piping shall be installed with a gray identification tape or wrap. Pipe identification shall include the contents of the piping system and an arrow indicating the direction of flow. Hazardous piping systems shall also contain information addressing the nature of the hazard. Pipe identification shall be repeated at intervals not exceeding 25 feet (7620 mm) and at each point where the piping passes through a wall, floor or roof. Lettering shall be readily observable within the room or space where the piping is located.