N.Y.C. Admin. Code § PC 703: Section PC 703: Building Drain
Where this section sits in the code
- New York City Administrative Code
- Title 28
- Chapter 6: New York City Plumbing Code
703.1 Building drain pipe near the water service.
Where the building drain is installed underground and within 5 feet (1524 mm) of the water service, as provided for in Section 603.2, the building drain pipe shall conform to one of the standards for, cast-iron pipe, copper or copper-alloy tubing, or ductile iron listed in
Table 702.3
.
703.2 Drainage pipe in filled ground.
Where a building drain is installed on filled or unstable ground, the drainage pipe shall conform to one of the standards for, cast-iron pipe, copper or copper-alloy tubing, ductile iron, nonasbestos fiber cement or concrete pipe listed in
Table 702.3
.
703.3 Sanitary and storm drains.
Where separate systems of sanitary drainage and storm drainage are installed in the same property, the sanitary and storm building drains shall be permitted to be laid side by side in one trench.
703.4 Existing building drains.
Existing building drains shall connect with new building drainage systems only where found by examination and test to conform to the new system in quality of material. The commissioner shall notify the owner to make the changes necessary to conform to this code.
703.5 Cleanouts on building drains.
Cleanouts on building
drains shall be located as set forth in Section
708
.
703.6 Combined sanitary and storm public sewer.
Where the public sewer is a combined system for both sanitary and storm water, the sanitary building drain shall be connected in accordance with Section 1109.1.
703.7 Building house traps.
Building house traps shall be installed on all building drains in accordance with Section 1002.6.
703.7.1 Fresh air inlets.
Every sanitary or combined building drain shall be provided with a fresh air inlet pipe connected to the building drain immediately upstream from and within 4 feet (1219 mm) of the building trap. Such connection shall be made in the same manner as prescribed in Section
905
for vent connections to horizontal drains, and the fresh air inlet pipe shall be extended to the outer air and shall be terminated in an open end at least 6 inches (152 mm) above grade. The open end shall be protected by a perforated metal plate permanently fixed in the mouth of the inlet and having an open ventilating area at least equal to the area of the pipe, or by a return bend with its unprotected open end at least 6 inches (152 mm) above grade, located inside the street line. The size of the fresh air inlet pipe shall be at least one-half the diameter of the building drain at the point of connection, but not less than 3 inches (76 mm).
703.7.2 Fresh air inlets located in flood hazard areas.
Fresh air inlets located in flood hazard areas shall be located above the design flood elevation in accordance with Section