711.1 Horizontal branch connections above or below vertical stack offsets.

If a horizontal branch connects to the stack within 2 feet (610 mm) above or below a vertical stack offset, and the offset is located more than four branch intervals below the top of the stack, the offset shall be vented in accordance with Section

907

.

711.1.1 Omission of vents for vertical stack offsets.

Vents for vertical offsets required by Section 711.1 shall not be required where the stack and its offset are sized as a building drain (see

Table 710.1(1)

, Column 5).

711.2 Horizontal stack offsets.

A stack with a horizontal offset located more than four branch intervals below the top of the stack shall be vented in accordance with Section

907

and sized as follows:

1. The portion of the stack above the offset shall be sized as for a vertical stack based on the total number of drainage fixture units above the offset.

2. The offset shall be sized in accordance with Section 710.1.1.

3. The portion of the stack below the offset shall be sized as for the offset or based on the total number of drainage fixture units on the entire stack, whichever is larger (see

Table 710.1(2)

, Column 4).

711.2.1 Omission of vents for horizontal stack offsets.

Vents for horizontal stack offsets required by Section 711.2 shall not be required where the stack and its offset are one pipe size larger than required for a building drain (see

Table 710.1(1)

, Column 5) and the entire stack and offset are not less in cross- sectional area than that required for a straight stack plus the area of an offset vent as provided for in Section

907

.

711.3 Offsets below lowest branch.

Where a vertical offset occurs in a soil or waste stack below the lowest horizontal branch, a change in diameter of the stack because of the offset shall not be required. If a horizontal offset occurs in a soil or waste stack below the lowest horizontal branch, the required diameter of the offset and the stack below it shall be determined as for a building drain in accordance with

Table 710.1(1)

.