Okla. Stat. tit. 63, § 63-701: Shooting galleries - Standards and specifications

Read at publisher ↗
Where this section sits in the code
  1. OK Code
  2. Title 63

(A) Open air shooting galleries constructed from and after the

effective date of this act shall conform to the following standards

and specifications:

(a) There shall be a backstop not less than seven and one-half

(7 1/2) feet high, which shall be constructed of steel of a

thickness not less than U.S. standard eight-gauge steel and shall be

well lapped at the joints; the backstop shall be not less than eight

(8) nor more than twenty-five (25) feet wide.

(b) Attached to each side of the backstop at ninety (90) degree

angles, extending toward the counter, shall be side walls of the

same height as the backstop, which side walls shall be constructed

of steel of a thickness not less than U.S. standard sixteen-gauge

steel and shall be from six (6) to twenty-five (25) feet in length.

In the event the steel side walls do not extend to the counter, the

remaining portion of the side walls shall be so constructed as to

prevent any person from getting into the line of fire.

(c) The inside edge of the counter from which the shooting

takes place shall be placed not less than twenty-five (25) feet from

the backstop or any metal target.

(d) All targets shall be placed not less than twelve (12)

inches from the ends of the backstop, and shall be not less than

twenty-four (24) inches from the top and not less than twelve (12)

inches from the bottom of the backstop.

(B) Closed shooting galleries constructed after the effective

date of this act shall be lawful of any size, provided that closed

shooting galleries shall be constructed so that they at least

conform to the minimum requirements of open air shooting galleries.