40 CFR Appendix D to Part 72: Appendix D to Part 72—Calculation of Potential Electric Output Capacity

Read at publisher ↗
Where this section sits in the code
  1. Title 40—Protection of Environment
  2. CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY
  3. SUBCHAPTER C—AIR PROGRAMS
  4. PART 72—PERMITS REGULATION

The potential electrical output capacity is calculated from the maximum design heat input from the boiler by the following equation:

For example:

(1) Assume a boiler with a maximum design heat input capacity of 340 million Btu/hr.

(2) One-third of the maximum design heat input capacity is 113.3 mmBtu/hr. The one-third factor relates to the thermodynamic efficiency of the boiler.

(3) To express this in MWe, the standards conversion of 3413 Btu to 1 kw-hr is used: 113.3 × 10 6 Btu/hr × 1 kw-hr / 3413 Btu × 1 MWe / 1000 kw = 33.2 MWe