GroundRules
← Search the law
Federal regulations · Through 2026-08-25 · Newer source version available

40 CFR Table 3 to Subpart Ec of Part 60: Table 3 to Subpart Ec of Part 60—Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies

Read at publisher ↗
Where this section sits in the code
  1. Title 40—Protection of Environment
  2. CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY
  3. SUBCHAPTER C—AIR PROGRAMS
  4. PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES
  5. Subpart Ec—Standards of Performance for New Stationary Sources: Hospital/Medical/Infectious Waste Incinerators

Operating parameters to be monitored Minimum frequency Control system

Data measurement Data recording Dry scrubber followed by fabric filter Wet scrubber Dry scrubber followed by fabric filter and wet scrubber

Maximum operating parameters:

Maximum charge rate Continuous 1 × hour ✔ ✔ ✔

Maximum fabric filter inlet temperature Continuous 1 × minute ✔ ✔

Maximum flue gas temperature Continuous 1 × minute ✔ ✔

Minimum operating parameters:

Minimum secondary chamber temperature Continuous 1 × minute ✔ ✔ ✔

Minimum dioxin/furan sorbent flow rate Hourly 1 × hour ✔ ✔

Minimum HCI sorbent flow rate Hourly 1 × hour ✔ ✔

Minimum mercury (Hg) sorbent flow rate Hourly 1 × hour ✔ ✔

Minimum pressure drop across the wet scrubber or minimum horsepower or amperage to wet scrubber Continuous 1 × minute ✔ ✔

Minimum scrubber liquor flow rate Continuous 1 × minute ✔ ✔

Minimum scrubber liquor pH Continuous 1 × minute ✔ ✔

Collected 2026-08-27T02:26:04Z. Source file · JSON

Browse this collection