40 CFR Table 3 to Subpart VVVV of Part 60: Table 3 to Subpart VVVV of Part 60—Requirements for Continuous Emission Monitoring Systems (CEMS)

Read at publisher ↗
Where this section sits in the code
  1. Title 40—Protection of Environment
  2. CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY
  3. SUBCHAPTER C—AIR PROGRAMS
  4. PART 60—STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES
  5. Subpart VVVV—Standards of Performance for Large Municipal Waste Combustors

For the following pollutants Use the following span values for your CEMS Use the following performance specifications for your CEMS During each relative accuracy test run, use the following methods to collect concurrent data

1. Particulate Matter For operation and correlation test, P.S. 11 in appendix B of this part and procedure 2 of appendix F to this part. Follow the test methods in Table 4 to Subpart VVVV.

For quarterly accuracy determinations, daily calibration drift tests, and each response correlation audit or relative response audit, procedure 2 of appendix F to this part

2. Nitrogen Oxides Control device outlet: 125 percent of the maximum estimated hourly nitrogen oxides emissions of the municipal waste combustor For operation, P.S. 2 in appendix B of this part and procedure 1 of appendix F of this part For relative accuracy, P.S. 2 in appendix B of this part and procedure 1 of appendix F of this part Method 7, 7A, 7C, 7D, or 7E in appendix A-4 to part 60 of this chapter.

For quarterly accuracy determinations and daily calibration drift tests, procedure 1 in appendix F of this part

3. Sulfur Dioxide Control device outlet: 50 percent of the maximum estimated hourly sulfur dioxide emissions of the municipal waste combustor For operation, P.S. 2 in appendix B of this part and procedure 1 of appendix F of this part For relative accuracy audit, P.S. 2 in appendix B of this part and procedure 1 of appendix F of this part Method 6, 6A, or 6C in appendix A-4 to part 60 of this chapter.

For quarterly accuracy determinations and daily calibration drift tests, procedure 1 in appendix F of this part

4. Carbon Monoxide 125 percent of the maximum estimated hourly carbon with monoxide emissions of the municipal waste combustor For operation, P.S. 4A in appendix B of this part and procedure 1 of appendix F of this part For relative accuracy audit, P.S. 4A in appendix B of this part and procedure 1 of appendix F of this part Method 10, 10A, or 10B in appendix A-4 to part 60 of this chapter.

For quarterly accuracy determinations and daily calibration drift tests, procedure 1 in appendix F of this part

5. Oxygen or Carbon Dioxide 25 percent oxygen or 20 percent carbon dioxide P.S. 3 in appendix B of this part Method 3A, or 3B in appendix A-2 to part 60 of this chapter, or, as an alternative for oxygen or carbon dioxide correction, the manual method portion of ASME PTC-19-10-1981—part 10.

6. Mercury Follow the approved site-specific monitoring plan For operation, P.S. 12A in appendix B of this part and procedure 5 of appendix F of this part, or the approved site-specific monitoring plan Follow the test methods in Table 4 to Subpart VVVV.

For relative accuracy audit, daily calibration, weekly system integrity check, quarterly audit, procedure 5 of appendix F of this part

7. Hydrogen chloride Follow the approved site-specific monitoring plan For operation, P.S. 18 in appendix B of this part and procedure 6 of appendix F of this part or the approved site-specific monitoring plan Follow the test methods in Table 4 to Subpart VVVV, except you may also use Methods 320 or 321 of appendix A to part 63.

For relative accuracy audit, daily calibration, quarterly audit, and other applicable quality assurance/quality control checks procedure 6 of appendix F of this part

8. Cadmium or Lead Follow the approved site-specific monitoring plan For operation, the approved site-specific monitoring plan Follow the test methods in Table 4 to Subpart VVVV.