40 CFR Table 4 to Subpart JJJJJJ of Part 63: Table 4 to Subpart JJJJJJ of Part 63—Performance (Stack) Testing Requirements

Read at publisher ↗
Where this section sits in the code
  1. Title 40—Protection of Environment
  2. CHAPTER I—ENVIRONMENTAL PROTECTION AGENCY
  3. SUBCHAPTER C—AIR PROGRAMS
  4. PART 63—NATIONAL EMISSION STANDARDS FOR HAZARDOUS AIR POLLUTANTS FOR SOURCE CATEGORIES
  5. Subpart JJJJJJ—National Emission Standards for Hazardous Air Pollutants for Industrial, Commercial, and Institutional Boilers Area Sources

As stated in § 63.11212, you must comply with the following requirements for performance (stack) test for affected sources:

To conduct a performance test for the following pollutant. . . You must. . . Using. . .

1. Particulate Matter a. Select sampling ports location and the number of traverse points Method 1 in appendix A-1 to part 60 of this chapter.

b. Determine velocity and volumetric flow-rate of the stack gas Method 2, 2F, or 2G in appendix A-2 to part 60 of this chapter.

c. Determine oxygen and carbon dioxide concentrations of the stack gas Method 3A or 3B in appendix A-2 to part 60 of this chapter, or ASTM D6522-00 (Reapproved 2005),a or ANSI/ASME PTC 19.10-1981. a

d. Measure the moisture content of the stack gas Method 4 in appendix A-3 to part 60 of this chapter.

e. Measure the particulate matter emission concentration Method 5 or 17 (positive pressure fabric filters must use Method 5D) in appendix A-3 and A-6 to part 60 of this chapter and a minimum 1 dscm of sample volume per run.

f. Convert emissions concentration to lb/MMBtu emission rates Method 19 F-factor methodology in appendix A-7 to part 60 of this chapter.

2. Mercury a. Select sampling ports location and the number of traverse points Method 1 in appendix A-1 to part 60 of this chapter.

b. Determine velocity and volumetric flow-rate of the stack gas Method 2, 2F, or 2G in appendix A-2 to part 60 of this chapter.

c. Determine oxygen and carbon dioxide concentrations of the stack gas Method 3A or 3B in appendix A-2 to part 60 of this chapter, or ASTM D6522-00 (Reapproved 2005), a or ANSI/ASME PTC 19.10-1981. a

d. Measure the moisture content of the stack gas Method 4 in appendix A-3 to part 60 of this chapter.

e. Measure the mercury emission concentration Method 29, 30A, or 30B in appendix A-8 to part 60 of this chapter or Method 101A in appendix B to part 61 of this chapter or ASTM Method D6784-02.a Collect a minimum 2 dscm of sample volume with Method 29 of 101A per run. Use a minimum run time of 2 hours with Method 30A.

f. Convert emissions concentration to lb/MMBtu emission rates Method 19 F-factor methodology in appendix A-7 to part 60 of this chapter.

3. Carbon Monoxide a. Select the sampling ports location and the number of traverse points Method 1 in appendix A-1 to part 60 of this chapter.

b. Determine oxygen and carbon dioxide concentrations of the stack gas Method 3A or 3B in appendix A-2 to part 60 of this chapter, or ASTM D6522-00 (Reapproved 2005),a or ANSI/ASME PTC 19.10-1981.a

c. Measure the moisture content of the stack gas Method 4 in appendix A-3 to part 60 of this chapter.

d. Measure the carbon monoxide emission concentration Method 10, 10A, or 10B in appendix A-4 to part 60 of this chapter or ASTM D6522-00 (Reapproved 2005) a and a minimum 1 hour sampling time per run.

a Incorporated by reference, see § 63.14.