46 CFR 108.445: Alarm and means of escape.
Where this section sits in the code
- Title 46—Shipping
- CHAPTER I—COAST GUARD, DEPARTMENT OF HOMELAND SECURITY
- SUBCHAPTER I-A—MOBILE OFFSHORE DRILLING UNITS
- PART 108—DESIGN AND EQUIPMENT
- Subpart D—Fire Extinguishing Systems
(a) Each CO2 system that has a supply of more than 136 kilograms (300 pounds) of CO2, except a system that protects a tank, must have an alarm that sounds for at least 20 seconds before the CO2 is released into the space.
(b) Each audible alarm for a CO2 system must have the CO2 supply for the system as its source of power and must be in a visible location in the spaces protected.
Collected 2026-08-27T02:26:22Z. Source file · JSON